Advanced control for efficient and reliable building climate management.
The controller is configured and serviced through the CCN user interface.
A dedicated user interface is not required for daily operation.
Configuration, diagnostics, and maintenance data are accessible via:
Level II communications port
Network Service Tool
ComfortVIEW™
ComfortWORKS®
System Pilot™
Touch Pilot™
Field wiring uses 18 to 22 AWG conductors.
The controller is rated as a NEC Class 2 device.
Supports the following inputs:
Space temperature sensor
Setpoint adjustment
Outdoor air temperature sensor
Indoor air quality sensor
Outdoor air quality / indoor humidity sensor
Compressor lockout
Fire shutdown
Supply fan status
Remote time clock / door switch
Enthalpy status
Provides control for:
Economizer
Fan
Cooling stages 1 & 2
Heating stages 1, 2, and 3
Exhaust / reversing valve / dehumidify / occupied functions
Power supply: 24 VAC ±15%, 60 Hz, 2‑wire
Rated at 40 VA
Normal operating range: 18–32 VAC
Minimum power consumption: 10 VA
| Document Name | Description | Document Type | Language | Action |
|---|---|---|---|---|
| Accessory and Kit Data | PremierLink Water Source Heat Pump Controller | English | Download | |
| Accessory and Kit Data | PremierLink Retrofit Split System Controller | English | Download | |
| Installation | 33CSPREMLK PremierLink™ Mounting Instructions | English | Download | |
| Product Data | 33CSPREMLK PremierLink™ Retrofit Rooftop Controller | English | Download |