Smart, energy-efficient water temperature monitoring for commercial HVAC systems.
The sensor is designed for water temperature monitoring in chilled water, hot water, and boiler systems.
The design supports retrofit applications, allowing existing thermistor installations to be integrated into the Rnet network.
Streamlined wiring and reduced controller input requirements simplify overall system design and installation.
Sensing Element
Temperature range: 20° to 120°F (‑5° to 50°C)
Accuracy: ±0.36°F (±0.2°C)
Sensor Accuracy
Temperature range: 20° to 120°F (‑5° to 50°C)
Accuracy: ±0.9°F (±0.5°C)
Enclosure Material
Polycarbonate, UL94V‑0
Enclosure Rating
NEMA 4 / IP66, UV‑rated
Enclosure Dimensions
Width: 5.0 in (12.7 cm)
Height: 4.15 in (10.54 cm)
Depth: 2.5 in (6.35 cm)
Probe Construction
304 stainless steel, 0.25 in (0.64 cm) diameter
Available in 2 in (5.08 cm) or 4 in (10.16 cm) lengths (specified at time of order)
Power Requirements
12 VDC @ 6 mA
Power Supply
Supplied via the 4‑conductor Rnet cable from the controller (+12 VDC @ 210 mA).
An external power supply may be used if additional power is required; the controller and external supply must share a common ground.
Communication Speed
115 kbps over the Rnet network
Our experts can help you choose the right commercial, residential, or light commercial HVAC solution from Carrier, Toshiba, and Viessmann.
ahi@ahi-carrier.com
+971 650 45700
Sharjah Research Technology and Innovation Park First Floor, Wing B – Sharjah United Arab Emirates
Fields marked * are required. We respond within one business day.