Smart climate monitoring starts here.
The sensor is designed to measure outdoor air temperature and humidity for HVAC ventilation, economizer, and control strategies.
The sensor integrates directly into the i‑Vu® system via the Rnet network, enabling scalable deployment without consuming additional controller inputs.
Temperature – Sensing Element
Range: 20° to 120°F (‑5° to 50°C)
Accuracy: ±0.36°F (±0.2°C)
Humidity – Sensing Element
Range: 10% to 90% RH
Accuracy: ±2.0% RH typical at 73°F (23°C)
Long‑term drift: < 0.5% per year
Temperature – Sensor Output
Range: 20° to 120°F (‑5° to 50°C)
Accuracy: ±0.9°F (±0.5°C)
Humidity – Sensor Output
Range: 10% to 90% RH
Accuracy: ±2.0% RH typical at 73°F (23°C)
Long‑term drift: < 0.5% per year
Enclosure Material
Polycarbonate, UL94V‑0
Enclosure Rating
NEMA 4 / IP66, UV‑rated
Enclosure Dimensions
Width: 5.0 in (12.7 cm)
Height: 4.15 in (10.54 cm)
Depth: 2.5 in (6.35 cm)
Sensor Probe Options
Temperature probe: Vented polycarbonate shield, 0.5 in (1.27 cm) OD, 1.2 in (3.05 cm) length
Temperature/Humidity probe: ABS with stainless‑steel filter, 1.0 in (2.5 cm) diameter, 2.4 in length
Sensing Element Shield
Vented polycarbonate shield, 0.5 in (1.27 cm) OD, 1.2 in (3.05 cm) length with ½‑inch NPT threads
Power Requirements
12 VDC @ 6 mA
Power Supply
Supplied via the 4‑conductor Rnet cable from the controller (+12 VDC @ 210 mA).
An external power supply may be used if required, and both supplies must share a common ground.
Communication Speed
115 kbps over the Rnet network
Our experts can help you choose the right commercial, residential, or light commercial HVAC solution from Carrier, Toshiba, and Viessmann.
ahi@ahi-carrier.com
+971 650 45700
Sharjah Research Technology and Innovation Park First Floor, Wing B – Sharjah United Arab Emirates
Fields marked * are required. We respond within one business day.