TruVu™ Controller

BMS & Control Carrier i-Vu Building Automation Controllers
TruVu™ Controller
General Purpose Controllers

TruVu™ Controller

High‑capacity, open‑protocol control for large‑scale HVAC and plant applications
The TruVu™ Controller (TV‑MPCXP1628‑NR) delivers powerful, scalable control for complex air‑side and water‑side HVAC systems, offering extensive I/O capacity, advanced BACnet interoperability, and seamless integration with the Carrier i‑Vu® Building Automation System.

TruVu™ Controller

The Carrier® TruVu™ MPCXP1628 controller provides multi-purpose monitoring and control for a variety of HVAC system applications. Flexible and versatile, it supports multiple I/O configurations for accomplishing both common and custom HVAC control strategies.

The TruVu MPCXP1628 controller features built-in routing and integration capabilities, 44 universal I/O points, and support for up to nine TruVu MPC I/O expansion modules for a total of 224 hardware control points.

The TruVu MPCXP1628-NR controller has the same features as the TruVu MPCXP1628, but does not support BACnet routing.

TruVu™ Controller

Comprehensive HVAC System Control

Supports full air‑side and water‑side system control using a robust library of factory‑engineered control programs.

Advanced Graphical Programming

Graphically programmable using SNAP, enabling fully customized control strategies for complex applications.

High‑Capacity Integration Platform

Supports up to 1,500 BACnet points and 200 Modbus points for large‑scale system integration.

Open BACnet Routing & Management

Provides BACnet routing, BBMD functionality, and Foreign Device Registration support.

Controller Type

BACnet Building Controller (B‑BC) and BACnet BBMD (B‑BBMD) compliant
(BACnet Router function not applicable to ‑NR version)

Communication Interfaces

Gigabit Ethernet for BACnet/IP, BACnet/Ethernet, and Modbus TCP/IP
Dual EIA‑485 ports for BACnet MS/TP or Modbus RTU
Ethernet service port for startup and troubleshooting

Inputs & Outputs

28 universal inputs (dry contact, thermistor, RTD, voltage, current, pulse)
16 universal outputs (voltage, current, or relay)
Hand/Auto/Off override switches and output status LEDs

Power Requirements

24 VAC or 24 VDC, Class 2 power
Internal protection via fast‑acting fuses

Document Name Description Document Type Language Action
Installation Guide TruVu MPCXP1628-NR Installation and Start-up Guide PDF English Download
Product Data TruVu™ TV-MPCXP1628, TV-MPCXP1628-NR BACnet Building Controller Product Data PDF English Download
What differentiates the TV‑MPCXP1628‑NR from the standard MPCXP controller?

The ‑NR variant removes routing capability while retaining high I/O density and BBMD functionality for large BAS deployments.

What types of systems is this controller best suited for?

It is ideal for large HVAC systems, central plants, and complex air‑side and water‑side applications requiring extensive I/O and integration.

Can this controller manage third‑party devices?

Yes. It supports large‑scale integration using BACnet and Modbus protocols.

Is this controller suitable for plant‑level control?

Yes. Its processing power and I/O capacity make it well suited for plant and enterprise‑level control strategies.

Similar Products

How Can We Help?

Have a question that doesn’t fit a specific category? Reach out to our team here for all other support
and information

    Become a Dealer

    Get directed to our Business Development team to start the authorization process and discuss sales support.

    Technical Assistance

    Get specialized help with system sizing, load
    calculation analysis, and technical data required for project design.

    Aftermarket Service

    Request support for warranty claims,
    scheduled maintenance, and genuine spare
    parts ordering.

    For more information : ahi@ahi-carrier.com