Advanced zone‑level intelligence for precise, energy‑efficient VVT control
The TruVu™ Dual IP VVT Zone Controller (TV‑VVTZC‑E2) delivers sophisticated, factory‑engineered control for VVT systems with dual‑IP networking, advanced comfort management, and seamless integration into the i‑Vu® Building Automation System.
The TruVu dual IP VVT zone controller provides zone level control for a variety of pressuredependent VVT applications. This completely programmable advanced controller features an integrated actuator for easy installation onto fan-powered or single-duct air terminals. It ships with Carrier factory engineered and tested applications for single zone and fan powered terminal control. The daisy chained BACnet IP communications deliver plug-andplay connectivity to the Carrier i-Vu building automation system.
BACnet Advanced Application Controller (B‑AAC) and BACnet Broadcast Management Device (B‑BBMD) compliant (BACnet 135‑2012, Protocol Rev. 15)
Dual 10/100 Mbps Ethernet ports (BACnet/IP), BACnet MS/TP via EIA‑485, USB for service and updates
4 universal inputs (dry contact, thermistor, pulse, or 0–10 VDC)
2 analog outputs (0–10 VDC)
3 digital outputs (dry contact)
Supports up to 2 Act Net smart actuators
45 in‑lb brushless DC actuator with integral precision airflow pressure sensor (0–2 in. H₂O)
It is designed for Variable Volume and Temperature (VVT) zone applications, providing precise zone‑level airside and comfort control.
Yes. It supports BACnet/IP and BACnet MS/TP, conforming to BACnet Advanced Application Controller standards.
Dual ports support flexible network topologies such as home‑run, daisy‑chain, or ring configurations, improving reliability and installation flexibility.
Yes. It supports zone‑level humidity control and demand‑controlled ventilation in accordance with ASHRAE® 62.1.