Surge protection for reliable BACnet MS/TP and RS‑485 network operation
The i‑Vu® Lightning Protection Board (PROT485) protects building automation controllers from electrical surges and transient events, helping ensure stable communication and long‑term reliability of RS‑485/BACnet MS/TP networks.
Not required (passive protection device)
Install at each point where network wiring enters or exits a building, or
One unit recommended within 250 ft (76 m) of each controller for maximum protection
Two replaceable 0.5 A time‑lag fuses:
F1: 3AG, 250 VAC, 0.5 A, T
F2: 3AG, 250 VAC, 0.5 A, T
22/24 AWG, single twisted shielded pair, low‑capacitance, CL2P‑rated cable