Surge protection for reliable BACnet MS/TP and RS‑485 network operation
The i‑Vu® Lightning Protection Board (PROT485) protects building automation controllers from electrical surges and transient events, helping ensure stable communication and long‑term reliability of RS‑485/BACnet MS/TP networks.
Network Device
Carrier's ancillary network devices ensure optimum performance for BACnet MS/TP and other EIA-485 networks. These devices install easily and work together to amplify data signals and provide surge protection, bias and termination to any EIA-485 network.
Not required (passive protection device)
Install at each point where network wiring enters or exits a building, or
One unit recommended within 250 ft (76 m) of each controller for maximum protection
Two replaceable 0.5 A time‑lag fuses:
F1: 3AG, 250 VAC, 0.5 A, T
F2: 3AG, 250 VAC, 0.5 A, T
22/24 AWG, single twisted shielded pair, low‑capacitance, CL2P‑rated cable
It protects RS‑485/BACnet MS/TP networks from lightning‑induced surges and electrical transients.
At each location where network wiring enters or exits a building, or within 250 ft of controllers for optimal protection.
Yes. The board includes replaceable 0.5 A time‑lag fuses to restore protection after a surge event.
It is strongly recommended for outdoor wiring, long cable runs, or lightning‑prone environments.